xupsRecepShedSecsWithRestart

  • 1.3.6.1.4.1.534.1.12.2.1.7
  • Access readwrite
  • Type Unknown
  • Unit seconds

Setting this value will cause the UPS output to turn off after the set number of seconds, then restart (after a UPS-defined 'down time') when the utility is again available. Unlike xupsRecepOffDelaySecs, which might or might not, this object always maps to the XCP 0x8A Load Dump & Restart command, so the desired shutdown and restart behavior is guaranteed to happen. Once set, this command cannot be aborted.

Table columns

10 objects
Oid Name Access Type
1.3.6.1.4.1.534.1.12.2.1.1 xupsRecepIndex readonly Unknown
1.3.6.1.4.1.534.1.12.2.1.2 xupsRecepStatus readonly on(1), off(2), pendingOff(3), pendingOn(4), unknown(5), reserved(6), failedClosed(7), failedOpen(8)
1.3.6.1.4.1.534.1.12.2.1.3 xupsRecepOffDelaySecs readwrite Unknown
1.3.6.1.4.1.534.1.12.2.1.4 xupsRecepOnDelaySecs readwrite Unknown
1.3.6.1.4.1.534.1.12.2.1.5 xupsRecepAutoOffDelay readwrite Unknown
1.3.6.1.4.1.534.1.12.2.1.6 xupsRecepAutoOnDelay readwrite Unknown
1.3.6.1.4.1.534.1.12.2.1.7 xupsRecepShedSecsWithRestart readwrite Unknown
1.3.6.1.4.1.534.1.12.2.1.8 xupsRecepHourlyPowerUsage readonly Unknown
1.3.6.1.4.1.534.1.12.2.1.9 xupsRecepCumulativePowerUsage readwrite Unknown
1.3.6.1.4.1.534.1.12.2.1.10 xupsRecepCumulativePowerUsageTimer readonly Counter32

Used by conformance groups

1 objects
  • 1.3.6.1.4.1.534.1.100.16 xupsRecepFullGroup

Comments