xupsRecepAutoOffDelay

  • 1.3.6.1.4.1.534.1.12.2.1.5
  • Access readwrite
  • Type Unknown
  • Unit seconds

The delay after going On Battery until the Receptacle is automatically turned Off. A value of -1 means that this Output should never be turned Off automatically, but must be turned Off only by command. Values from 0 to 30 are valid, but probably innappropriate. The AutoOffDelay can be used to prioritize loads in the event of a prolonged power outage; less critical loads will turn off earlier to extend battery time for the more critical loads. If the utility power is restored before the AutoOff delay counts down to 0 on an outlet, that outlet will not turn Off.

Table columns

10 objects
Oid Name Access Type
1.3.6.1.4.1.534.1.12.2.1.1 xupsRecepIndex readonly Unknown
1.3.6.1.4.1.534.1.12.2.1.2 xupsRecepStatus readonly on(1), off(2), pendingOff(3), pendingOn(4), unknown(5), reserved(6), failedClosed(7), failedOpen(8)
1.3.6.1.4.1.534.1.12.2.1.3 xupsRecepOffDelaySecs readwrite Unknown
1.3.6.1.4.1.534.1.12.2.1.4 xupsRecepOnDelaySecs readwrite Unknown
1.3.6.1.4.1.534.1.12.2.1.5 xupsRecepAutoOffDelay readwrite Unknown
1.3.6.1.4.1.534.1.12.2.1.6 xupsRecepAutoOnDelay readwrite Unknown
1.3.6.1.4.1.534.1.12.2.1.7 xupsRecepShedSecsWithRestart readwrite Unknown
1.3.6.1.4.1.534.1.12.2.1.8 xupsRecepHourlyPowerUsage readonly Unknown
1.3.6.1.4.1.534.1.12.2.1.9 xupsRecepCumulativePowerUsage readwrite Unknown
1.3.6.1.4.1.534.1.12.2.1.10 xupsRecepCumulativePowerUsageTimer readonly Counter32

Used by conformance groups

1 objects
  • 1.3.6.1.4.1.534.1.100.16 xupsRecepFullGroup