xupsRecepAutoOffDelay
The delay after going On Battery until the Receptacle is automatically turned Off. A value of -1 means that this Output should never be turned Off automatically, but must be turned Off only by command. Values from 0 to 30 are valid, but probably innappropriate. The AutoOffDelay can be used to prioritize loads in the event of a prolonged power outage; less critical loads will turn off earlier to extend battery time for the more critical loads. If the utility power is restored before the AutoOff delay counts down to 0 on an outlet, that outlet will not turn Off.
Table columns
10 objects| Oid | Name | Access | Type |
|---|---|---|---|
| 1.3.6.1.4.1.534.1.12.2.1.1 | xupsRecepIndex | readonly | Unknown |
| 1.3.6.1.4.1.534.1.12.2.1.2 | xupsRecepStatus | readonly | on(1), off(2), pendingOff(3), pendingOn(4), unknown(5), reserved(6), failedClosed(7), failedOpen(8) |
| 1.3.6.1.4.1.534.1.12.2.1.3 | xupsRecepOffDelaySecs | readwrite | Unknown |
| 1.3.6.1.4.1.534.1.12.2.1.4 | xupsRecepOnDelaySecs | readwrite | Unknown |
| 1.3.6.1.4.1.534.1.12.2.1.5 | xupsRecepAutoOffDelay | readwrite | Unknown |
| 1.3.6.1.4.1.534.1.12.2.1.6 | xupsRecepAutoOnDelay | readwrite | Unknown |
| 1.3.6.1.4.1.534.1.12.2.1.7 | xupsRecepShedSecsWithRestart | readwrite | Unknown |
| 1.3.6.1.4.1.534.1.12.2.1.8 | xupsRecepHourlyPowerUsage | readonly | Unknown |
| 1.3.6.1.4.1.534.1.12.2.1.9 | xupsRecepCumulativePowerUsage | readwrite | Unknown |
| 1.3.6.1.4.1.534.1.12.2.1.10 | xupsRecepCumulativePowerUsageTimer | readonly | Counter32 |
Used by conformance groups
1 objects- 1.3.6.1.4.1.534.1.100.16 xupsRecepFullGroup