xupsControlToBypassDelay

  • 1.3.6.1.4.1.534.1.9.5
  • Access readwrite
  • Type Unknown
  • Unit seconds

Setting this value to other than zero will cause the UPS output to go to Bypass after the number of seconds. If the Bypass is unavailable, this may cause the UPS to not supply power to the load. Setting it to 0 will cause an attempt to abort a pending shutdown.

Used by conformance groups

1 objects
  • 1.3.6.1.4.1.534.1.100.13 xupsControlFullGroup