xupsSendTrapType
The type of traps which will be sent to the requesting host; individual trap receivers will have individual values for this variable. The additional variables in types (3) and (4) are useful for determining which UPS is the source on multi-port network adapters, and for getting additional descriptive information. Types (1) through (4) are all SNMP version 1 trap PDUs. Values are: (1) stnd: Traps as defined in the Standard UPS MIB (RFC1628) and Generic (MIB II) traps as defined in RFC 1215. (2) xups: xupsTrapDefined Traps as defined in the PowerMIB and Generic (MIB II) traps as defined in RFC 1215. (3 Deprecated) stndPlus: same as stnd plus variables from the interface group and, where appropriate, xupsTrapMessage. (4 Deprecated) xupsPlus: xupsTrapPortN Traps (same as xups plus variables from the interface group) and, for authFail, xupsTrapMessage. (5 pxg: Traps as defined in the Power Xpert Gateway MIB (PXG-MIB).
Details
| 1 | stnd |
| 2 | xups |
| 3 | stndPlus |
| 4 | xupsPlus |
| 5 | pxg |
Used by conformance groups
1 objects- 1.3.6.1.4.1.534.1.100.15 xupsTrapControlFullGroup