This object enables(2) or disables(1) the alarms and traps related to the
availability and use of the secondary input of a dual-input UPS
(i.e., OnAlternatePowerSource and AltPowerNotAvailable).
To avoid nuisance alarms and traps, this object should be set to
disabled(1) when the UPS is not wired to a secondary source of power.
This object will only be implemented for UPSs with two sources of input
power, i.e., redundant AC feeds or a separate Bypass or Generator source.