xupsSecondaryInputWatch 1.3.6.1.4.1.534.1.3.7

This object enables(2) or disables(1) the alarms and traps related to the availability and use of the secondary input of a dual-input UPS (i.e., OnAlternatePowerSource and AltPowerNotAvailable). To avoid nuisance alarms and traps, this object should be set to disabled(1) when the UPS is not wired to a secondary source of power. This object will only be implemented for UPSs with two sources of input power, i.e., redundant AC feeds or a separate Bypass or Generator source.

Informations

Access Type
readwrite disabled(1), enabled(2)

Parent

1.3.6.1.4.1.534.1.3 xupsInput