For the Rectifier Standby Alarm (indicating output DC has been turned off);
Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
alarm condition.
Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
alarm condition.
Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
alarm condition.
Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
alarm condition.
Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
alarm condition.
Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
alarm condition.
Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
alarm condition.
Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
alarm condition.
Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigRect1ofNAlarm OID
to be activated if ONE rectifier fails in an N+1 system. It causes the alarm specified in the
dm3ConfigRect2ofNAlarm OID to be activated if TWO OR MORE rectifiers fail in an N+1 system.