sPDUOutletCtl 1.3.6.1.4.1.318.1.1.4.4.2.1.3

Getting this variable will return the outlet state. If the outlet is on, the outletOn (1) value will be returned. If the outlet is off, the outletOff (2) value will be returned. If the state of the outlet cannot be determined, the outletUnknown (4) value will be returned. If the outletUnknown condition should occur, all devices powered by the PDU should be shut down. The PDU's power should then be cycled to clear this condition. Setting this variable to outletOn (1) will turn the outlet on. Setting this variable to outletOff (2) will turn the outlet off. Setting this variable to outletReboot (3) will reboot the outlet. Setting this variable to outletOnWithDelay (5) will turn the outlet on after the sPDUOutletPowerOnTime OID has elapsed. This option is not valid for MasterSwitch firmware version 1.X. Setting this variable to outletOffWithDelay (6) will turn the outlet off after the sPDUOutletPowerOffTime OID has elapsed. This option is not valid for MasterSwitch firmware version 1.X. Setting this variable to outletRebootWithDelay (7) will turn the outlet off after the sPDUOutletPowerOffTime OID has elapsed, wait the sPDUOutletRebootDuration OID time, then turn the outlet back on. This option is not valid for MasterSwitch firmware version 1.X.

Informations

Access Type
readwrite outletOn(1), outletOff(2), outletReboot(3), outletUnknown(4), outletOnWithDelay(5), outletOffWithDelay(6), outletRebootWithDelay(7)

Parent

1.3.6.1.4.1.318.1.1.4.4.2.1 sPDUOutletControlEntry