sPDUMasterControlSwitch 1.3.6.1.4.1.318.1.1.4.2.1

Setting this OID to turnAllOnNow (1) will turn all outlets on immediately. Setting this OID to turnAllOnSequence (2) will turn all outlets on as defined by each outlet's sPDUOutletPowerOnTime OID value. Setting this OID to turnAllOff (3) will turn all outlets off immediately. Setting this OID to rebootAllNow (4) will reboot all outlets immediately. For MasterSwitch firmware version 1.X, setting this OID to rebootAllSequence (5) reboots all outlets, with power returned to the outlets in the sequence defined by each outlet's sPDUOutletPowerOnTime OID value. For MasterSwitch firmware version 2.X, setting this OID to rebootAllSequence (5) will cause a turnAllOffSequence to be performed. Once all outlets are off, the MasterSwitch will then delay the sPDUMasterConfigReboot OID time, and then perform a turnAllOnSequence. For MasterSwitch firmware version 2.X, setting this OID to turnAllOffSequence (7) will turn all outlets off as defined by each outlet's sPDUOutletPowerOffTime OID value. For MasterSwitch firmware version 1.X, setting this OID to turnAllOffSequence (7) will have no effect. Getting this OID will return the noCommand (6) value.

Informations

Access Type
readwrite turnAllOnNow(1), turnAllOnSequence(2), turnAllOffNow(3), rebootAllNow(4), rebootAllSequence(5), noCommand(6), turnAllOffSequence(7)

Parent

1.3.6.1.4.1.318.1.1.4.2 sPDUMasterControl