rPDU2DeviceControlCommand 1.3.6.1.4.1.318.1.1.26.4.4.1.4

Setting this OID to immediateAllOn (1) will turn all outlets on immediately. Setting this OID to delayedAllOn (2) will turn all outlets on as defined by each outlet's rPDU2OutletSwitchedConfigPowerOnTime OID value. Setting this OID to immediateAllOff (3) will turn all outlets off immediately. Setting this OID to immediateAllReboot (4) will cause an immediateAllOff command to be performed. Once all outlets are off, the Switched Rack PDU will then delay the rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform an immediateAllOn command. Setting this OID to delayedAllReboot (5) will cause a delayedAllOff command to be performed. Once all outlets are off, the Switched Rack PDU will then delay the largest rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform a delayedAllOn command. Setting this OID to noCommandAll (6) will have no effect. Setting this OID to delayedAllOff (7) will turn all outlets off as defined by each outlet's rPDU2OutletSwitchedConfigPowerOffTime OID value. Setting this OID to cancelAllPendingCommands (8) will cause all pending commands on the Switched Rack PDU to be cancelled. Getting this OID will return the noCommandAll (6) value.

Informations

Access Type
readwrite immediateAllOn(1), delayedAllOn(2), immediateAllOff(3), immediateAllReboot(4), delayedAllReboot(5), noCommandAll(6), delayedAllOff(7), cancelAllPendingCommands(8)

Parent

1.3.6.1.4.1.318.1.1.26.4.4.1 rPDU2DeviceControlEntry