xATSSwitchStatusOperationalMode 1.3.6.1.4.1.318.1.1.17.3.1.2

The current operating mode of the transfer switch. When the ATS is in automatic mode, generator starting and ATS transferring is all done automatically as needed based on the state of source 1. Automatic operation is halted when the ATS is in either of the notInAuto modes. A mode of notInAuto indicates that the automatic operation switch is in the disabled position, as indicated by the xATSSwitchStatusAutomaticOperationSwitch OID. The notInAutoAbnormal condition indicates that an abnormal condition has caused the transfer switch to halt automatic operation. In this case, traps can indicate the exact problem. In the case of notInAutoAbnormal, refer to the operation manual for details on how debug the condition and restore automatic operation.

Informations

Access Type
readonly automatic(1), notInAutoAbnormal(2), notInAuto(3), unknown(4)

Parent

1.3.6.1.4.1.318.1.1.17.3.1 xATSSwitchStatus