rARUConfigAruRemoteSetpoint 1.3.6.1.4.1.318.1.1.14.2.1.1.3

This OID defines the desired base airflow of the ARU, and sets the speed of the ARU fans when the temperature override is inactive. Values specified in cfm (cubic feet per minute) can be converted to metric values using the conversion factor: 1 cfm = 1.70 m^3/hr (cubic meters per hour). Values (1) through (9) are for support of legacy (1st generation) ARUs. Writing these values to a 2nd generation ARU will result in the following: A value greater than (9) will be ignored by a 1st generation ARU. aruOff (1) - Ignored aru85F-29C (2) - 1200 cfm aru90F-32C (3) - 800 cfm aru95F-35C (4) - 500 cfm aru100F-38C (5) - 400 cfm aru7kW (6) - 1200 cfm aru5kW (7) - 800 cfm aru3kW (8) - 500 cfm aru2kW (9) - 400 cfm NOTE: -1 will be returned if the ARU is not communicating.

Informations

Access Type
readwrite aruOff(1), aru85F-29C(2), aru90F-32C(3), aru95F-35C(4), aru100F-38C(5), aru7kW-1200cfm(6), aru5kW-800cfm(7), aru3kW-500cfm(8), aru2kW-300cfm(9), aru400cfm(10), aru600cfm(11), aru700cfm(12), aru900cfm(13), aru1000cfm(14), aru1400cfm(15), aru1600cfm(16), aru1800cfm(17), aru2000cfm(18)

Parent

1.3.6.1.4.1.318.1.1.14.2.1.1 rARUConfigEntry