airIRRP500UnitConfigIdleOnCoolFail 1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.15

When this OID value is (1) enable, the unit idles if it detects that it is blowing warm air into the cold aisle. The unit will attempt to restart at 5 minute intervals.

Informations

Access Type
readwrite enable(1), disable(2)

Parent

1.3.6.1.4.1.318.1.1.13.3.3.2.2.6 airIRRP500UnitConfig