airFMSysDehumSetpoint 1.3.6.1.4.1.318.1.1.13.1.4.7.3

The target value for the selected control sensor air for this mode. It must be at least 1.0 % RH above the humidification setpoint if a humidifier is installed. Measured in tenths of percent relative humidity. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration.

Informations

Access Type
readwrite

Parent

1.3.6.1.4.1.318.1.1.13.1.4.7 airFMSysDehumidify