rPDUOutletPhaseOverloadRestriction 1.3.6.1.4.1.318.1.1.12.3.2.1.1.2

This OID controls the behavior of a Switched Rack PDU phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding phase to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding phase to turn on if the rPDULoadConfigNearOverloadThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding phase to turn on if the rPDULoadConfigOverloadThreshold OID is exceeded.

Informations

Access Type
readwrite alwaysAllowTurnON(1), restrictOnNearOverload(2), restrictOnOverload(3)

Parent

1.3.6.1.4.1.318.1.1.12.3.2.1.1 rPDUOutletPhaseEntry