upsAdvTestRuntimeCalibration 1.3.6.1.4.1.318.1.1.1.7.2.5

Setting this variable to performCalibration(2) causes the UPS to discharge to calibrate the UPS. The test will only start if the battery capacity is 100%. The test runs until capacity is less than 25%. Setting this variable to cancelCurrentCalibration(3) after setting performCalibration(2) will cancel the current discharge. Setting this variable to noPerformCalibration(1) will have no effect. The value noPerformCalibration(1) will always be returned when the variable is read. The result of the calibration will be saved in upsAdvTestCalibrationResult.

Informations

Access Type
readwrite noPerformCalibration(1), performCalibration(2), cancelCurrentCalibration(3)

Parent

1.3.6.1.4.1.318.1.1.1.7.2 upsAdvTest