upsAdvControlUpsSleep
1.3.6.1.4.1.318.1.1.1.6.2.3
Setting this variable to putUpsToSleep(2) causes
the UPS to go to sleep for the time specified by
upsAdvConfigUpsSleepTime.
Setting this variable to putUpsToSleepGracefully(3)
causes the UPS to go to sleep for the time specified
by upsAdvConfigUpsSleepTime after a delay period.
This allows the host to shut down in a graceful manner.
If this UPS is an active member of a Synchronized Control
Group (SCG), the putUpsSyncGroupToSleep(4) command will perform
a Synchronized Sleep of all active Group members regardless
of their current AC output status. This unit's Power
Synchronization Delay, Shutdown Delay, Sleep Time,
and Return Delay will be used to execute the sleep command.
If this UPS is an active member of a SCG the
putUpsSyncGroupToSleepGracefully(5) command will perform a
Synchronized Sleep Gracefully of all active Group members
regardless of their current AC output status. This unit's
Power Synchronization Delay, Maximum Shutdown Time, Shutdown
Delay, Sleep Time, and Return Delay to execute the sleep
command.
When in sleep mode, the UPS will not provide output
power regardless of the input line state. Once the
specified time has elapsed, output power will be
restored.
Setting this value to noPutUpsToSleep(1) has no
effect.
The value noPutUpsToSleep(1) will always be returned
when the variable is read.