upsAdvControlUpsSleep 1.3.6.1.4.1.318.1.1.1.6.2.3

Setting this variable to putUpsToSleep(2) causes the UPS to go to sleep for the time specified by upsAdvConfigUpsSleepTime. Setting this variable to putUpsToSleepGracefully(3) causes the UPS to go to sleep for the time specified by upsAdvConfigUpsSleepTime after a delay period. This allows the host to shut down in a graceful manner. If this UPS is an active member of a Synchronized Control Group (SCG), the putUpsSyncGroupToSleep(4) command will perform a Synchronized Sleep of all active Group members regardless of their current AC output status. This unit's Power Synchronization Delay, Shutdown Delay, Sleep Time, and Return Delay will be used to execute the sleep command. If this UPS is an active member of a SCG the putUpsSyncGroupToSleepGracefully(5) command will perform a Synchronized Sleep Gracefully of all active Group members regardless of their current AC output status. This unit's Power Synchronization Delay, Maximum Shutdown Time, Shutdown Delay, Sleep Time, and Return Delay to execute the sleep command. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. Setting this value to noPutUpsToSleep(1) has no effect. The value noPutUpsToSleep(1) will always be returned when the variable is read.

Informations

Access Type
readwrite noPutUpsToSleep(1), putUpsToSleep(2), putUpsToSleepGracefully(3), putUpsSyncGroupToSleep(4), putUpsSyncGroupToSleepGracefully(5)

Parent

1.3.6.1.4.1.318.1.1.1.6.2 upsAdvControl