upsAdvControlRebootShutdownUps 1.3.6.1.4.1.318.1.1.1.6.2.2

Setting this variable to rebootShutdownUps(2) causes the UPS to shut off and turn back on (as long as good AC input power is available, otherwise the UPS will remain off until good AC input power is available). Setting this variable to rebootShutdownUpsGracefully(3) causes the UPS to shut off after a delay period and then turn back on. This allows the host to shut down in a graceful manner. If this UPS is an active member of a Synchronized Control Group (SCG) the rebootShutdownSyncGroupUps(4) command will perform a Synchronized Reboot of all active Group members regardless of their current AC output status. If applicable, this unit's Power Synchronization Delay, Shutdown Delay, Return Delay, Return Battery Capacity, and Return Battery Capacity Offset will be used to execute the Reboot command. If this UPS is an active member of a SCG the rebootShutdownSyncGroupUpsGracefully(5) command will perform a Synchronized Reboot of all active Group members regardless of their current AC output status. If applicable, this unit's Power Synchronization Delay, Maximum Shutdown Time, Shutdown Delay, Return Delay, Return Battery Capacity, and Return Battery Capacity Offset will be used to execute the Reboot command. Setting this value to noRebootShutdownUps(1) has no effect. The value noRebootShutdownUps(1) will always be returned when the variable is read.

Informations

Access Type
readwrite noRebootShutdownUps(1), rebootShutdownUps(2), rebootShutdownUpsGracefully(3), rebootShutdownSyncGroupUps(4), rebootShutdownSyncGroupUpsGracefully(5)

Parent

1.3.6.1.4.1.318.1.1.1.6.2 upsAdvControl