An ASCII string containing the 64 flags representing
the current active UPS specific faults for the Silcon
DP300E UPS models. If the Network Card is unable to
determine the values of the flags, this variable is set
to 'UNKNOWN'. If the connected UPS does not use this
variable, it is set to 'NOT SUPPORTED'.
The flags are numbered from 1 to 64, and read from left
to right. The bits are defined as follows:
Flag 1: Peak Current Limiter Active
Flag 2: Bypass Power Supply Fault
Flag 3: Delta Current Limiter Active
Flag 4: Fan Fault
Flag 5: High DC warning
Flag 6: Inverter Voltage Error
Flag 7: Parallel Synchronization Error
Flag 8: Second Power Supply Fault
Flag 9: Internal Power Supply Fault
Flag 10: <Not Used>
Flag 11: <Not Used>
Flag 12: <Not Used>
Flag 13: <Not Used>
Flag 14: Bypass Static Switch High Temperature
Flag 15: High Battery Temperature
Flag 16: Battery Weak
Flag 17: <Not Used>
Flag 18: System Locked in Operation Mode
Flag 19: RAM1 Memory Write Error
Flag 20: Memory Write Error
Flag 21: Communication to VQ Bypass Lost
Flag 22: Communication to VQ Output Lost
Flag 23: Communication to DMU Lost
Flag 24: Communication to Controller Lost
Flag 25: Communication to Parallel IF Lost
Flag 26: External Shutdown Accepted
Flag 27: DC Capacitor Charge Error
Flag 28: Communication to VQ Mains Lost
Flag 29: Bypass Synchronization Error
Flag 30: Charge Error
Flag 31: SII Aux Input Activiated
Flag 32: <Not Used>
Flag 33: Blown Inverter Fuse
Flag 34: Blown Rectifier Fuse
Flag 35: Auxilliary 1 Fault
Flag 36: <Not Used>
Flag 37: <Not Used>
Flag 38: <Not Used>
Flag 39: <Not Used>
Flag 40: <Not Used>
Flag 41: <Not Used>
Flag 42: <Not Used>
Flag 43: <Not Used>
Flag 44: <Not Used>
Flag 45: <Not Used>
Flag 46: High Temperature Charger Magnetic
Flag 47: <Not Used>
Flag 48: Battery Monitor Warning
Flag 49: Battery Monitor Alarm
Flag 50: <Not Used>
Flag 51: <Not Used>
Flag 52: <Not Used>
Flag 53: TSM 1/2/3 Temperature Shutdown
Flag 54: Charger 0/30 Temperature Warning
Flag 55: Charger 0/30 Temperature Shutdown
Flag 56: High Output Voltage
Flag 57: SSW Temperature Over 90
Flag 58: <Not Used>
Flag 59: Low Current Failure In AC Capacitors
Flag 60: <Not Used>
Flag 61: Advanced Battery Management Not Installed
Flag 62: <Not Used>
Flag 63: <Not Used>
Flag 64: <Not Used>